Product
Series
STC Series 3-phase AC
Synchronal Generator
This product is widely used in industries,
mines, communications, post and telecommunications, high buildings, ship-building
and field constructions as a main or auxiliary power supply.
This series generator adopts the 3-phase star connective method with neutral
point. The line voltage is 400V, phase voltage 230V, frequency 50Hz, Power
factor 0.8 (delay). According to the needs of users, we also may provide
other generators with 60Hz and other voltages.
This series generator links directly or through V belt with the prime
mover. The generator can rotate at both positive and negative directions,
and continuously operate at the rating conditions.
In order to make the generator operate normally, you must read this manual
carefully before use it.
I. Specification and Performance
This series generator adopts harmonic excitation. Besides the main
windings on the stator core, a set of harmonic windings is equipped, which
is connected to the windings in the magnetic field through a 3-phase or
single-phase bridge rectifier, to excite. Due to the third harmonic wave
voltage will go up correspondingly when generator has load, the self-exciting
constant voltage property can be reached without any complex automatic
voltage regulator.
Main technical parameters of generator:
Model |
Power |
Current(A) |
Number of poles |
Rotating speed (rpm) |
KVA |
KW |
STC-3 |
3.8 |
3 |
5.4 |
4 |
1500 |
STC-5 |
6.3 |
5 |
9 |
4 |
1500 |
STC-8 |
10 |
8 |
14.4 |
4 |
1500 |
STC-10 |
12.5 |
10 |
18 |
4 |
1500 |
STC-12 |
15 |
12 |
21.6 |
4 |
1500 |
STC-16 |
18.8 |
16 |
27 |
4 |
1500 |
STC-10 |
25 |
20 |
36 |
4 |
1500 |
STC-24 |
30 |
24 |
42 |
4 |
1500 |
STC-30 |
37.5 |
30 |
54 |
4 |
1500 |
STC-40 |
50 |
40 |
72 |
4 |
1500 |
STC-50 |
62.5 |
50 |
90 |
4 |
1500 |
STC-64 |
80 |
64 |
115 |
4 |
1500 |
STC-75 |
92.8 |
75 |
136 |
4 |
1500 |
STC-90 |
112.5 |
90 |
162 |
4 |
1500 |
STC-100 |
125 |
100 |
181 |
4 |
1500 |
STC-120 |
150 |
120 |
216 |
4 |
1500 |
STC-150 |
187.5 |
150 |
270 |
4 |
1500 |
Note: The rotating speed of the generator with 60Hz is 1800 rpm.
This series generator has excellent dynamic characteristics; it can directly
under non-load start the incompatible asynchronous cage motor without
adding any device.
II. Application Environment
This series generator is applicable to the following environments;
1. Attitude is not higher than 1000m.
2. Ambient temperature is not more than +40℃.
3. Relative humidity is not more than 85%.
4. Work field without conductive dust and corrosion gas destroying metal
insulation.
5. Work field without explosion risk.
When the ambient temperature is more than +40℃ or the attitude is higher
than 1000m, the output power of the generator shall correspondingly drop
down according to the technical standard.
III. Structure
This series generator adopts the rotating field type. The stator core
consists of 0.5 mm high quality laminated silicon sheet; the core of magnetic
pole consists of 1mm electric laminated steel plate. The wire adopts the
high strength enamel insulated wire. The isolative grade of stator is
H grade, while the isolative grade of rotator is B grade. The generator
with power 3KW-24KW is 3-phase third harmony wave. The switch box of generator
is located on the top of base; the connecting board, silicon rectifier
elements, 6.3V indicator and voltage meter are installed in the box. The
output cables are leaded out from the connective board through the outlet
hole at the back of the box, when connecting, you must pierce through
the seal film on the wire outlet hole plate with a small knife. The wiring
principle of the generator is shown in Figure 1. In the Figure 1, z4,
z5 as well z6, z7 are the harmony wave coils of secondary windings with
various number of turns. They can reach the aim to adjust the non-load
voltage through changing the positive or negative series connection of
the connecting terminals. When z4 connects to z6 and z7 connects to z8,
this is the situation that the both basic wave coils are be used independently.
When the generator delivers, the connecting terminals have been adjusted;
the user may change the connection of the basic wave coils according to
own need. The generator with power 30KW-150KW is the single-phase third
harmony wave. The terminal box of the generator is equipped with AVR automatic
voltage regulator and silicon rectifier elements. The wiring of the generator
is shown in Figure 2.
Main electric elements table of generator configuration:
No. |
Name |
Specification |
3KW-12KW |
15KW-24KW |
30KW-50KW |
64kw-150kw |
3 |
Magnetic field varistor |
BC1-150W 10Ω |
BC1-150W 7.5Ω |
No |
No |
5 |
Silicon diode |
2CZ-5A800V |
ZSQ-20A 1000V |
ZSO-50A 1000V |
8 |
Indicating lamp |
XD1-6.3V |
No |
No |
9 |
Voltage meter |
85L-0-500V |
69L13-0-500V |
No |
No |
IV. Notices before use
1. Connecting the output cable to the connecting board in the switch box
of the generator. The cable shall have sufficient section area to ensure
safe power transmission.
2. Open the rear cover of the machine shell; check whether the electric
brushes are normal.
3. Each output terminal shall be equipped with a switch and an appropriate
capacity fuser. Before the generator starts, any switch at output terminals
shall be at the open position.
V. Start and Stop
1. Start;
(1) Adjusting the magnetic field varistor on the switchboard to the
short position, that is turning to the highest position of the voltage
indicated by the arrow.
(2) Start the prime mover. When the rotating speed nears to the rating,
the generator will be able to establish the voltage through excitation.
Adjusting the rotating speed to a rotating speed that is a little higher
than the rating to compensate the drop-out of the rotating speed when
full load. At the same time adjust the magnetic field varistor until the
indication of the voltage meter reaches 400V.
(3) Close the switches at the output terminals; the normal power supply
may be achieved.
2. Stop
(1) Remove the loads at the output terminals and turn off the switches.
(2) Stop the prime mover.
(3) Adjust the magnetic field varistor to the short position.
3. Notices:
(1) Avoid the short circuit of the output terminals of the generator,
because the short circuit may damage the rectifier elements.
(2) The loads shall be removed before stop. If stop with load, the residual
magnetism may be lost. When use nest time, you must re-magnetize.
(3) After stop, adjust the magnetic field varistor to the short position
to avoid the difficulty of establishing voltage when start next time.
VI. Maintenance, Check and Repair
1. General maintenance
(1) Protecting the generator from wetting. When store, it shall be placed
at the dry position. When place on the earth or concrete floor, you must
put woods under it. When store, you must cover it with oilskin to avoid
the entering of wet.
(2) Avoid any intrusion of dirt, water, metal scrap or other foreign material
when store or in running.
(3) No article is allowed to cover on the generator. So doing will prevent
the heat from dissipation to cause the generator overheat damage.
(4) Pay attention to the ventilation and overheat of generator, the indications
of current and voltage. Avoid overload.
(5) Often check the abnormal spark on the bus rings. If find the abnormal
noise when running you shall immediately check.
(6) Where moisture and dust are too much or containing flammable gas the
generator shall be not used.
(7) After 1000-1500 hours of operation, the grease in the ball or roller
bearings shall be changed, at least they shall be changed two times each
year. The adding grease quantity shall be the 2/3 of bearing cover, too
much is not allowed. The adding grease tools shall be clean and the hybrid
use is not allowed for different greases. The recommended lubricant grease
is No. 3 lithium grease. The temperatures of the ball or roller bearings
shall be not higher than 55℃.
(8) The silicon rectifier elements shall be held ventilation well; on
the radiator and shell no article that prevent heat from dissipation is
allowed to cover.
(9) Often clean the dirt on the silicon rectifier elements and check the
fastened screws on the silicon rectifier elements for loose.
(10) Check the connecting terminals in the control penal for sealing off,
broken ends or loose.
2. Check and Repair
In order to ensure the safe running of the generator, and find and eliminate
the potential accident cause, the regular check is necessary for the generator.
Generally make a check each three months, an overhaul each year.
(1) Common check and repair items
① Remove the window cover and clean dust and dirt in the generator.
The better cleaning method is using the compression air, whose pressure
is not higher than 2 atm., to blow.
② Clean the surface of bus ring. First using the coarse cloth (the cotton
goods without cotton wools and fabrics) dipping with some kerosene rub
the surface, then using the clean coarse cloth rub it until dry.
③ Remove the bearing cover and check the lubricant grease, if find uneven
color, change it.
④ Check the carbon brush for wearing and adjust the pressure of spring,
change the worn carbon brush.
(2) Overhaul items
① Use a 500V megohmmeter to measure the insulated resistance. If the
resistance to ground is less than 1 MΩ, the drying shall be done.
② If the surface of bus ring has become rough or worn, we shall recover
its smooth through machining and turning cutting.
③ Remove the ball or roller bearings and clean them with kerosene; their
turning shall be flexible and no noise. Add some grease and re-assemble.
④ Check the contact situation of wiring parts and fasten the wiring
nuts.
⑤ Clean the internal part of the generator throughout with blowing air,
especially the bus ring and the joint.
(3) Notices when check and repair
① Removed parts shall be stored in a container to avoid any lose due
to random place.
② Main parts such as rotator, end cover, machine base, bus ring, carbon
brush etc. must be placed carefully to avoid any damage due to impact.
③ The removed connecting terminals shall be marked to avoid incorrect
connection when re-wiring.
④ The removed bearing and cover shall be covered with clean paper to
avoid the intrusion of dirt. If find dirt, you must change all the greases.
⑤ The arcs between the carbon brush and the bus ring shall fit, otherwise
shall re-polish.
⑥ After finish assembly of generator, using hand rotate the rotator,
check noise and flexible.
⑦ The screws on the end covers and the magnetic poles must be fastened
in a diagonal crisscross method.
3. Troubleshooting
Troubles |
Causes |
Treatment |
| 1. No ignition |
① Wiring fault
② Too low residual magnetism voltage (the normal residual magnetism
voltage, V line>10V, V phase>9V)
③ Contact between electric brush and bus ring is not good or pressure
of electric brush is insufficient.
④ Brush holder is rust so that can't slide up and down. |
① Check wiring according to wiring diagram, and re-wiring.
② Use 9V battery to charge, when charging, the anode of battery
connects to F1(+), the cathode connects to F2(-).
③ Clean surface of bus ring, polish the arcs of brush surface and
bus ring surface to make them fit. Increase pressure of brush spring.
④ Use No.00 emery cloth rub internal surface of brush holder or
replace it if damage. |
| 2. Generator overheat |
① Overload
② Magnetic field coil is short circuit
③ Stator winding is short circuit
④ Friction between stator and rotator |
① Monitor ammeter often, hold current below rating.
② Replace
③ Replace coil of short circuit
④ Check shaft, bearing room and bearing for loose |
| 3. Bearing overheat |
① Bearing is excessive wear
② Grease specification is not the recommended, or adding grease
is too much, or impurity in grease. |
① Replace
② Clean bearing with kerosene, adding grease shall be 2/3 of bearing
room, too much is no suitable. |
| 4. Establish voltage difficultly, and can't
establish voltage when loading |
A circuit is open among Z1-Z4 |
Using universal meter check the open circuit,
and re-weld it。 |
| 5. When idle, no voltage is output, when loading, voltage
is too low |
A circuit is short among Z1-Z4 |
Using universal meter check the short circuit, and replace
it |
Installation Size STC3KW∽50KW
Table I
Model |
Installation size |
H |
A |
A/2 |
B |
C |
D |
E |
F |
G |
K |
STC-3 |
132 |
216 |
108 |
178 |
89 |
32 |
80 |
10 |
27 |
12 |
STC-5 |
160 |
254 |
127 |
178 |
18 |
38 |
33 |
15 |
STC-8 |
254 |
STC-10 |
180 |
279 |
139.5 |
203 |
121 |
42 |
110 |
12 |
37 |
STC-12 |
203 |
STC-16 |
241 |
STC-20 |
200 |
318 |
159 |
228 |
133 |
48 |
STC-24 |
267 |
14 |
42.5 |
19 |
Installation Size STC64KW∽150KW
Table II
Model |
Installation size |
H |
A |
B |
C1 |
D |
E |
F |
G |
K |
M |
N |
L1 |
STC-30 |
225
|
356
|
286
|
294 |
φ60
|
110 |
18
|
53 |
19 |
440 |
416 |
-5
|
STC-40 |
428 |
409
|
STC-50 |
356 |
STC-64 |
250
|
406
|
349 |
250 |
φ70 |
110 |
20 |
62.5
|
24
|
552
|
532
|
21
|
STC-75 |
406 |
STC-90 |
280
|
457
|
368
|
243
|
φ70 |
110 |
20 |
62.5 |
20
|
21
|
STC-100 |
STC-120 |
330
|
457
|
279 |
463
|
φ80 |
140 |
22 |
71
|
20.5
|
26
|
STC-150 |
STC-200 |
STC-250 |
|